Vendor: General Electric

GE Hydran M2 Dissolved Gas Analysis (DGA) Monitoring Device

SKU: Hydran M2
In stock
Description

Product Description

  • Manufacturer: GE Vernova
  • Product Type: Dissolved Gas Analysis (DGA) Monitoring Device
  • Application: Transformer health monitoring in power utilities and industrial plants

Specifications

  • Gas Sensors:
    • Hydrogen (general fault gas)
    • Carbon Monoxide (overheated paper)
    • Acetylene (arcing)
    • Ethylene (overheated oil)
  • Moisture Sensor: Measures water in the oil, indicating insulating paper degradation or leaking gaskets
  • Communication: Supports a wide range of communication protocols including Modbus®, DNP 3.0, and Ethernet
  • Power Supply: Compatible with worldwide power supply standards
  • Installation: Easily installs on a single transformer oil valve without extra piping or pumps

Features

  • Continuous Monitoring: Provides real-time data on fault gases and moisture levels
  • Configurable Alarms: Two alarm levels (Alert and Alarm) for increasing severity
  • Self-Test: Automatic self-test every 15 days to detect faults
  • Expandable: Can connect additional sensors for load, oil temperature, and other parameters
  • Compatibility: Works with various transformer oil types, including ester-based fluids
  • Asset Management: Integrates with GE’s Perception™ Fleet software for data analysis and trend monitoring