Vendor:
Triconex
3636T | Triconex | Digital Relay Output Module
Description
Description
The 3636T module is engineered for non-critical points that are incompatible with high-side solid-state output switches. It is commonly used for applications such as interfacing with annunciator panels. The module receives output signals from the main processors, votes on the signals, and drives individual relays based on the voted data.
Specifications
- Type: Non-triplicated Relay Output Module.
- Number of Points: 32 non-commoned points.
- Voltage Range: Up to 125 VAC/VDC.
- Current Load: Maximum 2A per point.
- Minimum Load: 10 mA at 5 VDC.
- Switching Power: 2,000 VA or 150 watts (resistive load).
- Point Isolation: 1,900 VDC.
- Fuses: 2.5A fast-acting fuse per output.
- Diagnostic Indicators: Output status, module status (PASS, FAULT, ACTIVE).
- Dimensions: Compact design for easy integration.
- Weight: Approximately 0.1 kg.
Features
- Loopback circuit verifies relay operation independently of load presence.
- Ongoing diagnostics ensure operational status of the module.
- Supports hot-spare modules for redundancy.
- Modular design for easy installation and maintenance.
- Suitable for applications requiring high reliability and safety.
3636T | Triconex | Digital Relay Output Module